| Fluid Types | Single medium, including a non-conductive medium and most clean liquids. |
|---|---|
| Pipe Sizes | 50 MM - 300 MM |
| Flow Accuracy | 1% |
| Repeatability | 0.2% of the measured value |
| Flow Range | 0.09 ft/s ~ 40 ft/s |
| Measurement Parameters | Instantaneous energy, totalized energy, instantaneous flow, totalized flow, supply temperature and return temperature. |
| Electronic Enclosures | ABS (Wall mounted enclosure) |
| IP Rating | IP65 |
| Memory | EEPROM |
| Data Logging | 8 GB removable memory card |
| Power Supply | 24 VDC / 2A |
| Ambient Temperature | 0C - 60C |
| Operating Temperature Range (Fluid) | 5F to 176F (-15C to 80C) |
| Standard Outputs | 4-20 mA, pulse |
| Network Connection | Modbus RTU RS 485 |
| Process Connections | ANSI 150 Flanges |
| Nominal Pressure | 1.6 MPa |
| Flow Tube | Standard: Stainless Steel |
| Flange Material | Standard: Carbon Steel Optional: Stainless Steel |
| Temperature Sensors | PT 1000 |
ABOUT
Introducing our Mial MUF 1200 Inline Ultrasonic Flow & Btu meter, engineered for unparalleled precision in measuring water flow and thermal energy. Perfect for a variety of applications, from HVAC to industrial processes, these meters incorporate advanced ultrasonic technology for consistent, accurate data. Each unit is rigorously calibrated, ensuring reliability and efficiency in your operations. Our commitment to excellence is reflected in every meter, certified to meet your specific needs
Feature
FAQ
Q. Can the meter be connected to BMS or SCADA systems?
A.Yes. The MUF(B) 1200 can be integrated with:
Q. Does the meter require periodic maintenance?
The MUF(B) 1200 has no moving parts, resulting in low maintenance requirements. Periodic inspection and cleaning may be recommended depending on fluid quality.
Q. How does the BTU meter calculate energy?
The meter calculates energy based on:
Q. Why choose Mial MUF 1200?
A. Key advantages include:





Price:
Price 173000.0 INR / Unit